| Power supply | 24 Vac/dc |
| Design (panel size) | DIN |
| Control input | Universal |
| Auxiliary digital input | Yes |
| Output - relay | 0x |
| Output for SSR | 2x |
| Producer | Ascon Tecnologic |
DIN module for data acquisition with alarms. Two independent channels - collection of two independent values.
Characteristic features:
- Compact dimensions (DIN width 22.5mm)
- Two adjustable process inputs, one digital input
- Two digital outputs
- Two additional adjustable digital inputs or outputs
- Power and RS485 on the side for better modularity
- Pull-out electronics
- Backup configuration and parameters for easy replacement and maintenance
| TECHNICAL SPECIFICATIONS | |
|---|---|
| 2x universal input | Thermocouples L, J, T, K, S, R, B, N, E, Ni-NiMo, W3, W5 Pt100 voltage 0/10...50 mV current 0/4...20 mA Self linearization and IR probes (J.K) |
| 1x digital input 2x additional adjustable digital input or output | NPN, TTL, voltage free |
| 4x digital output 2x additional adjustable digital input or output | Switching relay 2A 250Vac Triac 1A 250Vac sSR output 0...5Vdc ±20% 30mA |
| Power supply | 24 Vac/Vdc Converter 18Vdc ±20% 30mA |
| Functions | Acquisition and transmission of process variables Configuration and parameter backup with automatic recovery (DX master) |
| Alarms | Up to 4 adjustable alarms |
| Communication | RS485 ModBus RTU and J-bus (slave) |
| Dimensions | 22.5 x 99 x 114.5 mm |
This online store saves cookies that help its proper functioning. By using our services, you agree to their use.