Dixell XC650CX 0C05F controller for condensing units with 5 outputs and Digital Scroll compressor control

size 32x74 mm, power supply 12 Vacdc, 2x analog input 4..20mA/0..5V/NTC, 5x output relay + analog output
Dixell XC650CX 0C05F controller for condensing units with 5 outputs and Digital Scroll compressor control
Dixell XC650CX 0C05F controller for condensing units with 5 outputs and Digital Scroll compressor control
Dixell XC650CX 0C05F controller for condensing units with 5 outputs and Digital Scroll compressor control (1)
192 EUR 159 EUR excl. VAT
On request
In person in Prague:on requestWith a delivery company:on request
Code1D-170-082PNrozměr 32x74mm, napájení 12Vac/dc, vstup 2x 4..20mA/PTC/NTC, výstup 5x relé ProducerDixellWarranty2 years

Connection cable Dixell CAB/CJ15 1,5m

Connection cable Dixell CAB/CJ15 1,5m
In stock
2,88 EUR excl. VAT3,48 EUR

Connection cable Dixell CAB/CJ30 3m

Connection cable Dixell CAB/CJ30 3m
In stock
4,93 EUR excl. VAT5,97 EUR

Dixell RG-C gasket

Dixell RG-C gasket
In stock
1,03 EUR excl. VAT1,24 EUR

Dixell NG6 NTC temperature sensor

Dixell NG6 NTC temperature sensor
In stock
4,73 EUR excl. VAT5,72 EUR

PTC temperature probe Dixell S6.S - 2 m

PTC temperature probe Dixell S6.S - 2 m
In stock
9,46 EUR excl. VAT11,44 EUR

HotKey 32 programming key for Dixell controllers

HotKey programming key for Dixell controllers
In stock
6,58 EUR excl. VAT7,96 EUR
  • for control of condensing units with Digital Scroll compressor
  • 2x analogue input NTC/4..20mA/0..5V - temperature/pressure
  • 5x output relay
  • for two refrigeration circuits, 5 compressors/fan units in total
  • analogue output
  • Connection cables CW15-KIT, CAB/CJ15, CAB/CJ30 are not included in the controller and must be ordered as a separate item


Dixell XC600 Series Comparison:

XC645CX XC645D XC650CX XC660D
Power 12, 24 Vacdc 230 Vac 12, 24 Vacdc 230 Vac
Analog inputs:
Suction 0..5V, 4..20mA, NTC 0..5V, 4..20mA, NTC 0..5V, 4..20mA, NTC 0..5V, 4..20mA, NTC
Displacement 0..5V, 4..20mA, NTC 0..5V, 4..20mA, NTC 0..5V, 4..20mA, NTC 0..5V, 4..20mA, NTC
Configurable input NTC NTC NTC 0..5V, 4..20mA, NTC
Digital inputs:
Low pressure switch 1 1 1 1
High pressure switch 1 1 1 1
Alarm 4 5 4 6
Configurable 1 2 1 2
Outputs:
Relay 4x 5A 4x 5A 5x 5A 6x 5A
Digital™ compressor Triac Triak
Fr.inverter for compressor Optional 4..20mA, 0..10V Optional 4..20mA, 0..10V Optional 4..20mA, 0..10V
Fr.inverter for fans Optional 4..20mA, 0..10V Optional 4..20mA, 0..10V Optional 4..20mA, 0..10V Optional 4..20mA, 0..10V
Load 12V/40mA 12V/40mA
Other features:
Communication TTL RS485 TTL RS485
Remote keypad VC660 VC660
Connection kit CWC15-KIT, CWC30-KIT,
CAB/CJ15, CAB/CJ30
CW15-KIT, CW25-KIT,
CAB/CJ15, CAB/CJ30

Power supply12 Vac/dc
Design (panel size)32 x 74 mm
Type of regulationPI
Control inputUniversal
Auxiliary digital inputYes
Output - relay5x
Analog outputYes
Display digit colourTwo colours
ProducerDixell

The Dixell XC650CX is a combined condensing unit controller with the ability to control up to 5 compressors and fans simultaneously, with frequency control of both compressor and fan output.

Features and functions of the Dixell XC650CX controllers:

  • Digital™, multi-stage, variable capacity, semi-hermetic, scroll, screw type compressors
  • Selectable control as proportional zone or neutral zone
  • Floating condensing pressure control depending on external temperature
  • High configurability and flexibility
  • Automatic shutdown of compressors in case of high condensing pressure / temperature
  • Silent mode function of fans during night
  • Automatic lubricant transfer system in the circuit
  • Safer control with low and high pressure safety switch
  • Adjustable refrigerant type for pressure - temperature conversion
  • Memory for the last 10 alarms
  • HotKey/ProgToolKit connector for easy and quick programming
  • Connection to Xweb monitoring system
  • Maximum power consumption only 5 VA
  • Dual display with 17 status icons

TECHNICAL SPECIFICATIONS
Dimensions front panel 32x74 mm, depth 70mm
Mounting in panel, hole 29x71mm
Power supply 12Vac/dc ±10%
Consumption max. 5 VA
Coverage IP65 (front panel), otherwise IP20
Inputs 2 x NTC/4..20mA/0..5V (optional parameter)
7 x digital input
Outputs 5 x SPST 5(3)A relay, 250Vac
2x analogue output 4÷20mA or 0÷10V
oA6 open collector output 12V, 40mA
TTL, ModBus - RTU
Resolution 0.1°C; 1°F; 0.1bar; 1 PSI;
Accuracy ±0.7 °C ±1 digit
DescriptionTechnical parametersDownload

This online store saves cookies that help its proper functioning. By using our services, you agree to their use.

Detailed settingsAllow everything