| Cable length | No cable |
| Communication Bus | RS485 |
| Temperature sensor type | NTC |
| Measured quantity | Temperature + humidity |
| Measuring part of the sensor | Spatial |
| Designation | Wall-mounted |
| Producer | Dixell |
| Measured temperature range | worse than -30..+80°C |
The Dixell XH50P and XH55P probes are designed to measure temperature/relative humidity and also allow calculation of the dew point of the space in which they are placed. By connecting outputs (relay or analog signal), it can also function as a simple thermostat.
Thanks to these features, it can be used to control anti-condensation heating for cooling, as a simple thermostat, hygrostat or as a simple temperature and humidity sensor for air conditioning. The probe can be connected to other elements via relay, analogue output or RS485.
With the Dixell XH55P sensors, the desired value can be set within ±3°C using the rotary knob (this value can be changed by the Ltr and Utr parameters). When the knob is fully disabled, all outputs are disabled.
| TECHNICAL PARAMETERS | |
|---|---|
| Power supply | 12...24 Vac or 12...40 Vdc |
| Power input | max 3VA |
| Inputs | NTC 10K?@25°C digital input |
| Outputs | 8A switching (optional 16A switching) 0...10 Vdc output resistance 47 ?, 10mA maximum RS485 communication |
| Measurement and control range | Humidity 1...99% RH ±3.5% Temperature -40...+80 °C |
| Operating temperature | -10...+60 °C |
| Dimensions | 80 x 120 x 25.6mm |