Power supply | 12 Vac/dc |
Design (panel size) | 32 x 74 mm |
Type of regulation | On/off |
Control input | Temperature sensor |
Auxiliary digital input | Yes |
Output - relay | 4x |
Communication Bus | RS485 |
Display digit colour | Red |
Producer | Dixell |
XR170C/D controllers with temperature control, active defrost and fan control are designed for cooling units operating at medium and low temperatures. They are equipped with four relay outputs for compressor, defrost, fan control and in addition a configurable auxiliary relay (alarm or lighting etc.).
The controllers have an input for PTC or NTC sensors with user configurable options. The thermostats are connected to the monitoring system via RS485 serial interface and ModBUS-RTU protocol. All types are equipped with configurable digital input, door contact and buzzer. Parameters can be easily copied with the HOT KEY programming key.
Input | 3x PTC thermistor (-50...150°C) or NTC (-40...110°C) |
Other inputs | 1 x digital config. voltage-free input 1 x door contact |
Outputs | compressor - switching relay 8(3) A / 250 V defrost - switching relay 8(3) A / 250 V fan - switching relay 8(3) A / 250 V alarm - switching relay 8(3) A / 250 V |
Other outputs | rS485 output for monitoring buzzer |
Power supply | 12 Vacdc ±10 % |
Power input | approx. 3VA |
Accuracy | ± 0,5 °C |
Sampling time | 1s |
Operating conditions | 0...60°C, 20...85% humidity |
Front panel cover | IP65 with RG-C seal |