Dixell XR60CX 5N0C1 cooling controller with fan control

size 32x74mm, power supply 230Vac, input 2x PTC/NTC (-50..150 °C), 3x output relays 20A+8A+8A
Dixell XR60CX 5N0C1 cooling controller with fan control
Dixell XR60CX 5N0C1 cooling controller with fan control
Dixell XR60CX 5N0C1 cooling controller with fan control
84,39 EUR 69,74 EUR excl. VAT
In stock
In person in Prague:nowWith a delivery company:tomorrow
Code1D-080-545PNrozměr 32x74mm, napájení 230 Vstř, vstup 3x PTC/NTC, 3x relé (20A pro kompresor)ProducerDixellWarranty2 years

Sensfox CM-02 IoT monitoring system for Dixell

Sensfox CM-02 IoT monitoring system for Dixell
In stock
169 EUR excl. VAT205 EUR

Mon-Sys D2C monitoring system for Dixell Prime

Mon-Sys D2C monitoring system for Dixell Prime
In stock
161 EUR excl. VAT195 EUR

Dixell NG6 NTC temperature sensor

Dixell NG6 NTC temperature sensor
In stock
4,64 EUR excl. VAT5,61 EUR

PTC temperature probe Dixell S6.S - 2 m

PTC temperature probe Dixell S6.S - 2 m
In stock
9,27 EUR excl. VAT11,22 EUR

Dixell MDP/CX back cover for CX controllers

Dixell MDP/CX back cover for CX controllers
In stock
2,38 EUR excl. VAT2,88 EUR
  • For cooling applications with defrost and fan control
  • 3 outputs for compressor, fan, defrost
  • 2 inputs for NTC / PTC temperature sensors
  • Option to connect 2 more PTC / NTC sensors

Dixell Prime CX Series Comparison:

XR30CX XR35CX XR40CX XR60CX XR64CX XR70CX XR72CX XR75CX
Power supply 12, 24 Vacdc,
230 Vac
230 Vac 12, 24 Vacdc,
230 Vac
12, 24 Vacdc,
230 Vac
12, 24 Vacdc,
230 Vac
12, 24 Vacdc,
230 Vac
12, 24 Vacdc,
230 Vac
230 Vac
Analog inputs:
Thermostat NTC, PTC NTC, Pt1000 NTC, PTC NTC, PTC NTC, PTC NTC, PTC NTC, PTC NTC, Pt1000
Defrosting NTC, Pt1000 NTC, PTC NTC, PTC NTC, PTC NTC, PTC NTC, PTC NTC, Pt1000
Defrost 2 NTC, PTC
Capacitor NTC, PTC to HotKey NTC, Pt1000 NTC, PTC to HotKey NTC, PTC on HotKey NTC, PTC on HotKey NTC, PTC on HotKey NTC, PTC to HotKey NTC, Pt1000
Digital inputs:
Alarm, defrost start, AUX, door contact, pressure switch, temperature sensor Configurable Configurable Configurable Configurable Configurable Configurable Configurable Configurable
Alarm, defrost start, AUX, door contact, pressure switch Configurable Configurable
Output relay:
Compressor 8A, 20A 8A, 16A 8A, 20A 8A, 16A, 20A 8A, 16A 8A, 16A 8A, 16A 8A, 16A
Compressor 2 8A, 16A
Defrosting 8A 8A 8A, 16A 8A, 16A 8A, 16A 8A
Defrosting 2 8A, 16A
Fans 5A, 8A 5A, 16A 5A, 16A 5A, 16A 5A
Lighting / Alarm 8A 8A 8A, 16A 8A
Defogging 8A, 16A
Mixing
Other features:
Communication TTL RS485 TTL TTL TTL TTL TTL RS485
RTC Optional Optional Optional Optional

Power supply230 Vac
Design (panel size)32 x 74 mm
Type of regulationOn/off
Control inputTemperature sensor
Auxiliary digital inputYes
Output - relay3x
Display digit colourRed
ProducerDixell

The Dixell XR60CX models are microprocessor-based controllers, particularly suitable for medium or low temperature cooling applications. They are suitable for panel mounting and have dimensions of 32 × 74 mm. They feature three relay outputs: for compressor, fan and defrost control (can be either electric or reverse cycle - hot steam). They are equipped with up to four inputs for PTC or NTC temperature sensors. One for temperature control, the second located on the evaporator (used to control the defrost termination temperature and fan control), the third and fourth are optional (connected to the HOT KEY connector and to the dig.input) to signal a condensing temperature alarm or just to display any temperature on the remote display. The units also have a digital input for alarm signalling, for switching on the auxiliary output or for defrost triggering. The digital input can be optionally configured for a fourth temperature sensor.
The HOT KEY output can be used to connect the instrument (using the external XJ485-CX module) to a Dixell XWEB monitoring system. The instruments can be fully configured with parameters that can be easily programmed using the keypad or HOT KEY programming key. The compressor output relay has a load rating of 20A (8A inductive load). The other two relays have a load rating of 8A (3A inductive load).

TECHNICAL PARAMETERS
Enclosure front panel 32 × 74 mm, depth 60 mm
Mounting in-panel, hole 29 x 71 mm
Front panel enclosure IP65
Power supply voltage 230 Vac, ± 10% 50/60 Hz
Power input 3 VA max
Display 3-digit, red LED, digit height 14.2 mm
Inputs 2x PTC (-50 to 150 °C) or NTC (-40 to 110 °C)
Possibility to connect 2 more PTC / NTC sensors
Additional inputs digital voltage-free contact
Output - compressor switching relay 20(8) A, 250 Vac
Output - defrost switching relay 8(3) A 250Vac
Output - fan switching relay 8(3) A, 250 Vac
Step 0.1 °C or 1 °C (adjustable)
Accuracy ± 0.7 °C ±1 digit
DescriptionTechnical parametersDownload