Dixell XR64CX 5N0C0 dual evaporator cooling controller

For cooling applications with one compressor and two evaporators with separate defrost control.
Dixell XR64CX 5N0C0 dual evaporator cooling controller
Dixell XR64CX 5N0C0 dual evaporator cooling controller
Dixell XR64CX 5N0C0 dual evaporator cooling controller
91,71 EUR 75,79 EUR excl. VAT
In stock
In person in Prague:nowWith a delivery company:tomorrow
Code1D-080-555PNrozměr 32x74mm, napájení 230Vac, vstup 3x PTC/NTC, 4x relé, 2x odtávání pro 2 výparníkyProducerDixellWarranty2 years

Sensfox CM-02 IoT monitoring system for Dixell

Sensfox CM-02 IoT monitoring system for Dixell
In stock
169 EUR excl. VAT205 EUR

Mon-Sys D2C monitoring system for Dixell Prime

Mon-Sys D2C monitoring system for Dixell Prime
In stock
161 EUR excl. VAT195 EUR

PTC temperature probe Dixell S6.S - 2 m

PTC temperature probe Dixell S6.S - 2 m
In stock
9,27 EUR excl. VAT11,22 EUR

Dixell NG6 NTC temperature sensor

Dixell NG6 NTC temperature sensor
In stock
4,64 EUR excl. VAT5,61 EUR

Dixell MDP/CX back cover for CX controllers

Dixell MDP/CX back cover for CX controllers
In stock
2,38 EUR excl. VAT2,88 EUR
  • For cooling applications with two evaporators
  • Dual defrost, common fan control
  • 4 Outputs: compressor, fan, 2x defrost
  • Up to 4 PTC/NTC inputs

Dixell Prime CX Series Comparison:

XR30CX XR35CX XR40CX XR60CX XR64CX XR70CX XR72CX XR75CX
Power supply 12, 24 Vacdc,
230 Vac
230 Vac 12, 24 Vacdc,
230 Vac
12, 24 Vacdc,
230 Vac
12, 24 Vacdc,
230 Vac
12, 24 Vacdc,
230 Vac
12, 24 Vacdc,
230 Vac
230 Vac
Analog inputs:
Thermostat NTC, PTC NTC, Pt1000 NTC, PTC NTC, PTC NTC, PTC NTC, PTC NTC, PTC NTC, Pt1000
Defrosting NTC, Pt1000 NTC, PTC NTC, PTC NTC, PTC NTC, PTC NTC, PTC NTC, Pt1000
Defrost 2 NTC, PTC
Capacitor NTC, PTC to HotKey NTC, Pt1000 NTC, PTC to HotKey NTC, PTC on HotKey NTC, PTC on HotKey NTC, PTC on HotKey NTC, PTC to HotKey NTC, Pt1000
Digital inputs:
Alarm, defrost start, AUX, door contact, pressure switch, temperature sensor Configurable Configurable Configurable Configurable Configurable Configurable Configurable Configurable
Alarm, defrost start, AUX, door contact, pressure switch Configurable Configurable
Output relay:
Compressor 8A, 20A 8A, 16A 8A, 20A 8A, 16A, 20A 8A, 16A 8A, 16A 8A, 16A 8A, 16A
Compressor 2 8A, 16A
Defrosting 8A 8A 8A, 16A 8A, 16A 8A, 16A 8A
Defrosting 2 8A, 16A
Fans 5A, 8A 5A, 16A 5A, 16A 5A, 16A 5A
Lighting / Alarm 8A 8A 8A, 16A 8A
Defogging 8A, 16A
Mixing
Other features:
Communication TTL RS485 TTL TTL TTL TTL TTL RS485
RTC Optional Optional Optional Optional

Power supply230 Vac
Design (panel size)32 x 74 mm
Type of regulationOn/off
Control inputTemperature sensor
Auxiliary digital inputYes
Output - relay4x
Display digit colourRed
ProducerDixell

The Dixell XR64CX models are microprocessor-based controllers, particularly suitable for medium or low temperature cooling applications. They are designed for cooling applications with one compressor and two evaporators with separate defrost control. They are suitable for panel mounting and have dimensions of 32 × 74 mm.

They are equipped with four relay outputs: for compressor control, fan control and dual defrost for individual evaporators (can be either electric or reverse cycle - hot steam). They are equipped with up to four inputs for PTC or NTC temperature sensors. One for temperature control, a second and third located on the evaporator (used for defrost termination temperature control and fan control) and a fourth is optional (connected to the HOT KEY connector and to the dig.input) for signaling a condensing temperature alarm or just to display any temperature on a remote display. The units also have a digital input for alarm signalling, for switching on the auxiliary output or for defrost triggering. The digital input can be optionally configured for a fourth temperature sensor. The HOT KEY output can be used to connect the instrument (using the external XJ485-CX module) to a Dixell XWEB monitoring system.

The instruments can be fully configured with parameters that can be easily programmed using the keypad, the HOT KEY programming key or the ProgToolKit interface. The compressor output relay has a load rating of 8A (3A inductive load). The other two relays have an ampere rating of 8A (3A inductive load).

TECHNICAL PARAMETERS
Enclosure front panel 32 × 74 mm, depth 60 mm
Mounting in-panel, hole 29 x 71 mm
Front panel enclosure IP65
Power supply voltage 230 Vac, ± 10% 50/60 Hz
Power input 3 VA max
Display 3-digit, red LED, digit height 14.2 mm
Inputs 3x PTC (-50 to 150 °C) or NTC (-40 to 110 °C)
Additional PTC / NTC sensor can be connected
Additional inputs digital voltage-free contact
Output - compressor switching relay 8(3), 250 Vac
Output - defrost 1 switching relay 8(3) A; 250Vac
Output - defrost 2 switching relay 8(3) A; 250Vac
Output - fan switching relay 5(2) A, 250 Vac
Step 0.1 °C or 1 °C or 1 °F (adjustable)
Accuracy ±0.7 °C ±1 digit
DescriptionTechnical parametersDownload