Dixell XT100D Series Comparison:
XT110D | XT111D | XT120D | XT121D | XT130D | XT131D | XT141D | XT160D | |
Power supply | 24Vacdc, 230Vac | 24Vacdc, 230Vac | 24Vacdc, 230Vac | 24Vacdc, 230Vac | 24Vacdc, 230Vac | 24Vacdc, 230Vac | 24Vacdc, 230Vac | 24Vacdc, 230Vac |
Inputs: | ||||||||
NTC, PTC, Pt100, TcJ, TcK, TcS, or 4..20mA, 0..1V, 0..10V | 1x configurable | 1x configurable | 1x configurable | 1x configurable | 1x configurable | 1x configurable | 1x configurable | 1x configurable |
Digital input | 1x configurable | 1x configurable | 1x configurable | 1x configurable | 1x configurable | 1x configurable | 1x configurable | 1x configurable |
Output relay: | ||||||||
Stage 1 | no 8A / nc 5A | no 8A / nc 5A | no 8A / nc 5A | no 8A / nc 5A | no 8A / nc 5A | no 8A / nc 5A | no 8A / nc 5A | no 8A / nc 5A |
Grade 2 | no 8A / nc 5A | no 8A / nc 5A | no 8A / nc 5A | no 8A / nc 5A | no 8A / nc 5A | no 8A / nc 5A | ||
Grade 3 | no 8A / nc 5A | |||||||
Grade 4 | 8A | |||||||
Alarm | no 8A / nc 5A | no 8A / nc 5A | no 8A / nc 5A | no 8A / nc 5A | ||||
Other features: | ||||||||
Communication | TTL | TTL | TTL | TTL | TTL | TTL | TTL | TTL |
Analog output | 4..20mA, 0..10V optional | 4..20mA, 0..10V optional | 4..20mA, 0..10V optional | 4..20mA, 0..10V optional | 4..20mA, 0..10V optional | 4..20mA, 0..10V optional | 4..20mA, 0..10V optional | 4..20mA, 0..10V optional |
Alarm buzzer | Optional | Optional | Optional | Optional | Optional | Optional | Optional | Optional |
Power supply | 230 Vac |
Design (panel size) | DIN |
Type of regulation | On/off |
Control input | Analog signal |
Auxiliary digital input | Yes |
Output - relay | 1x |
Display digit colour | Red |
Producer | Dixell |
Dixell XT110D models (DIN rail mounted) are two-state ON/OFF controllers for controlling temperature, humidity, pressure or other variables.
The analog input can be set to 4÷20mA, 0÷1V, 0÷10V signals.
All XT series controllers are equipped with a digital input, optional buzzer and can be programmed quickly and easily using the HOT KEY programming key. In the basic version there is also a TTL output for connecting the controller to serial communication.
TECHNICAL PARAMETERS | |
---|---|
Power supply | 230 Vac ±10 %, 50/60 Hz |
Power consumption | approx. 3VA |
Accuracy at 25 °C | better than ± 0.5 °C |
Sampling time | 1s |
Front Panel Coverage | IP65 with RG-C seal |
Input | current 4 to 20 mA voltage input 0 to 1/10 V |
Other inputs | digital input - voltage-free contact |
Output | switching relay 8(3) A / 250 V |
Other outputs | TTL output for serial communication (output for HOT KEY programming key) |