Dixell XT100C Series Comparison:
| XT110C | XT111C | XT120C | XT121C | XT130C | XT131C | XT141C | |
| Power supply | 12, 24 Vacdc, 230 Vac | 12, 24 Vacdc, 230 Vac | 12, 24 Vacdc, 230 Vac | 12, 24 Vacdc, 230 Vac | 12, 24 Vacdc, 230 Vac | 12, 24 Vacdc, 230 Vac | 12, 24 Vacdc, 230 Vac |
| Inputs: | |||||||
| NTC, PTC, Pt100, TcJ, TcK, TcS, or 4..20mA, 0..1V, 0..10V | 1x configurable | 1x configurable | 1x configurable | 1x configurable | 1x configurable | 1x configurable | 1x configurable |
| Digital input | 1x configurable | 1x configurable | 1x configurable | 1x configurable | 1x configurable | 1x configurable | 1x configurable |
| Output relay: | |||||||
| Stage 1 | 8A | 8A | 8A | 8A | 8A | 8A | 8A |
| Grade 2 | 8A | 8A | 8A | 8A | 8A | ||
| Grade 3 | |||||||
| Grade 4 | |||||||
| Alarm | 8A | 8A | 8A | 8A | |||
| Other features: | |||||||
| Communication | TTL | TTL | TTL | TTL | TTL | TTL | TTL |
| Analog output | |||||||
| Alarm buzzer | Optional | Optional | Optional | Optional | Optional | Optional | Optional |
| Power supply | 24 Vac/dc |
| Design (panel size) | 32 x 74 mm |
| Type of regulation | On/off |
| Control input | Analog signal |
| Auxiliary digital input | Yes |
| Output - relay | 3x |
| Display digit colour | Red |
| Producer | Dixell |
The Dixell XT121C (in panel) models are two-state ON/OFF controllers for regulating temperature, humidity, pressure, or other variables.
Their two output control relays can be set for two-stage control (e.g. Stage 1 heats a little, Stage 2 heats a lot), but they can also be set for direct or inverted operation without a neutral zone (e.g. Stage 1 output for heating, Stage 2 output for cooling). The third output relay is an alarm relay and allows reporting or handling of alarm conditions. Their analog input can be set to signals of 4÷20mA, 0÷1V, 0÷10V type.
All XT series controllers are equipped with a digital input, optional buzzer and can be programmed quickly and easily using the HOT KEY programming key. In the basic version there is also a TTL output for connecting the controller to serial communication.
| TECHNICAL PARAMETERS | |
|---|---|
| Power supply | 24 Vacdc ±10 %, 50/60 Hz |
| Power input | approx. 3VA |
| Accuracy at 25 °C | better than ± 0.5 °C |
| Sampling time | 1s |
| Front Panel Coverage | IP65 with RG-C seal |
| Input (model XT1**AU) | 4 to 20 mA current voltage 0 to 1/10 V |
| Other inputs | digital input - voltage-free contact |
| Output | 2x switching relay 8(3) A / 250 V 1x alarm switching relay 8(3) A / 250 V |
| Other outputs | TTL output for serial communication (output for HOT KEY programming key) |
This online store saves cookies that help its proper functioning. By using our services, you agree to their use.