Dixell XT100C Series Comparison:
XT110C | XT111C | XT120C | XT121C | XT130C | XT131C | XT141C | |
Power supply | 12, 24 Vacdc, 230 Vac | 12, 24 Vacdc, 230 Vac | 12, 24 Vacdc, 230 Vac | 12, 24 Vacdc, 230 Vac | 12, 24 Vacdc, 230 Vac | 12, 24 Vacdc, 230 Vac | 12, 24 Vacdc, 230 Vac |
Inputs: | |||||||
NTC, PTC, Pt100, TcJ, TcK, TcS, or 4..20mA, 0..1V, 0..10V | 1x configurable | 1x configurable | 1x configurable | 1x configurable | 1x configurable | 1x configurable | 1x configurable |
Digital input | 1x configurable | 1x configurable | 1x configurable | 1x configurable | 1x configurable | 1x configurable | 1x configurable |
Output relay: | |||||||
Stage 1 | 8A | 8A | 8A | 8A | 8A | 8A | 8A |
Grade 2 | 8A | 8A | 8A | 8A | 8A | ||
Grade 3 | |||||||
Grade 4 | |||||||
Alarm | 8A | 8A | 8A | 8A | |||
Other features: | |||||||
Communication | TTL | TTL | TTL | TTL | TTL | TTL | TTL |
Analog output | |||||||
Alarm buzzer | Optional | Optional | Optional | Optional | Optional | Optional | Optional |
Power supply | 230 Vac |
Design (panel size) | 32 x 74 mm |
Type of regulation | On/off |
Control input | Temperature sensor |
Auxiliary digital input | Yes |
Output - relay | 3x |
Display digit colour | Red |
Producer | Dixell |
The Dixell XT121C (in panel) models are two-state ON/OFF controllers for regulating temperature, humidity, pressure, or other variables.
Their two output control relays can be set for two-stage control (e.g. Stage 1 heats a little, Stage 2 heats a lot), but they can also be set for direct or inverted operation without a neutral zone (e.g. Stage 1 output for heating, Stage 2 output for cooling). The third output relay is an alarm relay and allows reporting or handling of alarm conditions. Their analog input can be set to PTC, NTC, Pt100, J, K, S thermocouple signals.
All XT series controllers are equipped with a digital input, optional buzzer and can be programmed quickly and easily using the HOT KEY programming key. The basic version also includes a TTL output for connecting the controller to serial communication.
TECHNICAL PARAMETERS | |
---|---|
Power supply | 230 Vac ±10 %, 50/60 Hz |
Power consumption | approx. 3VA |
Accuracy at 25 °C | better than ± 0.5 °C |
Sampling time | 1s |
Front Panel Coverage | IP65 with RG-C seal |
Input | PTC (NTC) thermistor(-50 to 140°C) Pt 100 resistive (-100 to 500°C) J - thermocouple (0 to 600°C) K - thermocouple (0 to 1200°C) S - thermocouple (0 to 1400°C) |
Other inputs | digital input - Voltage-free contact |
Output | 2x switching relay 8(3) A / 250 V 1x alarm switching relay 8(3) A / 250 V |
Other outputs | TTL output for serial communication (output for HOT KEY programming key) |