Dixell XT100C Series Comparison:
XT110C | XT111C | XT120C | XT121C | XT130C | XT131C | XT141C | |
Power supply | 12, 24 Vacdc, 230 Vac | 12, 24 Vacdc, 230 Vac | 12, 24 Vacdc, 230 Vac | 12, 24 Vacdc, 230 Vac | 12, 24 Vacdc, 230 Vac | 12, 24 Vacdc, 230 Vac | 12, 24 Vacdc, 230 Vac |
Inputs: | |||||||
NTC, PTC, Pt100, TcJ, TcK, TcS, or 4..20mA, 0..1V, 0..10V | 1x configurable | 1x configurable | 1x configurable | 1x configurable | 1x configurable | 1x configurable | 1x configurable |
Digital input | 1x configurable | 1x configurable | 1x configurable | 1x configurable | 1x configurable | 1x configurable | 1x configurable |
Output relay: | |||||||
Stage 1 | 8A | 8A | 8A | 8A | 8A | 8A | 8A |
Grade 2 | 8A | 8A | 8A | 8A | 8A | ||
Grade 3 | |||||||
Grade 4 | |||||||
Alarm | 8A | 8A | 8A | 8A | |||
Other features: | |||||||
Communication | TTL | TTL | TTL | TTL | TTL | TTL | TTL |
Analog output | |||||||
Alarm buzzer | Optional | Optional | Optional | Optional | Optional | Optional | Optional |
Power supply | 24 Vac/dc |
Design (panel size) | 32 x 74 mm |
Type of regulation | On/off |
Control input | Analog signal |
Auxiliary digital input | Yes |
Output - relay | 2x |
Display digit colour | Red |
Producer | Dixell |
The Dixell XT130C models are two-stage ON/OFF controllers with a neutral zone for temperature, humidity and pressure control. They are equipped with two control outputs for direct and inverse operation (e.g. heating and cooling). The analog input can be set to analog linear signals 4...20mA, 0...1V, 0...10V.
Control description:
Some rooms require a type of control that is succinctly expressed by the motto "cool in summer, heat in winter". These are e.g. warehouses with poor thermal insulation.
The controller controls 2 relays, each in ON/OFF mode. The principle of this control precludes both outputs from operating simultaneously.
The relay for the heating is ON when the current temperature is lower than the desired temperature, when the temperature reaches the desired value the heating is switched off.
If the temperature continues to rise , neither output is switched on within a certain distance of the setpoint (neutral zone). If the temperature rises above the neutral zone, cooling is switched on. It operates until the temperature drops to the desired value, then switches off. If the temperature continues to fall within the neutral zone, no output is switched on; if the temperature falls below the neutral zone, the heating is switched on. The neutral zone (parameter db) is located symmetrically to the setpoint (SET), so that its boundaries lie at (SET-db/2) and (SET+db/2).
All XT series controllers are equipped with a digital input, optional buzzer and can be programmed quickly and easily using the HOT KEY programming key. The basic version also includes a TTL output for connecting the controller to serial communication.
TECHNICAL PARAMETERS | |
---|---|
Power supply | 24 Vacdc ±10 %, 50/60 Hz |
Power input | approx. 3VA |
Accuracy at 25 °C | better than ± 0.5 °C |
Sampling time | 1s |
Front Panel Coverage | IP65 with RG-C seal |
Input | current 4 to 20 mA voltage input 0 to 1/10 V |
Other inputs | digital input - voltage-free contact |
Output | 2x switching relay 8(3) A / 250 V |
Other outputs | TTL output for serial communication (output for HOT KEY programming key) |