Measuring transformer 0...25/50A with 4 to 20 mA output

It converts the signal from the measuring transformer to a normalized current signal of 4...20 mA. It works with TrueRMS value when measuring AC current.
Measuring transformer 0...25/50A with 4 to 20 mA output
Measuring transformer 0...25/50A with 4 to 20 mA output
Measuring transformer 0...25/50A with 4 to 20 mA output (1)
Measuring transformer 0...25/50A with 4 to 20 mA output (2)
126 EUR 104 EUR excl. VAT
In stock
In person in Prague:nowWith a delivery company:tomorrow
Code1P-700-125PNvstup 0 až 25/50A, výstup 4..20mA, napájení 11...30VdcProducerPixsysWarranty2 years
  • High precision
  • Input/output galvanically isolated
  • For measurement of direct (DC) and alternating (AC) currents
  • TrueRMS measurement of AC current value
  • 25A or 50A range selectable
  • Bipolar output selectable
  • Cannot measure direction of AC current flow
Power supply12-24 Vac/dc
Control inputAnalog signal
Output - relay0x
Analog outputYes
ProducerPixsys

Measuring transformer of direct and alternating currents, converting the signal value to a normalized analogue current signal of 4...20mA. The characteristics of these converters ensure high accuracy of temperature reading due to the 12-bit precision A/D converter. The device is similar in function and appearance to standard active measurement transformers, but is capable of measuring TRMS DC and AC current components. The transformer is powered by a 4-20mA current loop and therefore does not require a direct power supply. It is the first loop-powered Hall transformer with 0.5% accuracy on the market.

TECHNICAL PARAMETERS
Dimensions 46.1 x 63 x 26.3 mm
Power supply loop current supply
Range 11...30 Vdc
Output 4...20 mA
Measuring range 50Arms (±50A) or 25Arms (±25A) adjustable
Maximum conversion error 0.1% of range or 0.2°C (higher of the two)
Measurement True RMS
Resolution 12bits
0.5% of range
Isolation 3kV
Response time (10...90%) approx. 1000 ms
Overload 2kA impulse, 300A DC
Standards CE, EN 61000-6-4, EN 61000-6-2, EN 61010-1
Operating conditions -40...+85°C
30...90% RH non-condensing
Hysteresis 0.15% of range
DescriptionTechnical parametersDownload

This online store saves cookies that help its proper functioning. By using our services, you agree to their use.

Detailed settingsAllow everything