Temperature and voltage converter to 4 to 20 mA signal on DIN rail with NFC

Converts the signal from Pt100, Ni100 temperature sensors, K, S, R, J, T, N, B, E thermocouples and voltage to a normalized current signal of 4...20 mA. Measured value recorder function. Programming and data download via NFC wireless transmission (RFid).
Temperature and voltage converter to 4 to 20 mA signal on DIN rail with NFC
Temperature and voltage converter to 4 to 20 mA signal on DIN rail with NFC
Temperature and voltage converter to 4 to 20 mA signal on DIN rail with NFC (1)
Temperature and voltage converter to 4 to 20 mA signal on DIN rail with NFC (2)
Temperature and voltage converter to 4 to 20 mA signal on DIN rail with NFC (3)
104 EUR 85,92 EUR excl. VAT
In stock
In person in Prague:nowWith a delivery company:tomorrow
Code1P-700-115PNvstup Pt100, NI100, TC K, S, R, J, T, N, B, E a napětí, výstup 4..20mA, napájení 6...32VdcProducerPixsysWarranty2 years

Pixsys RFid converter programmer

Pixsys RFid converter programmer
On request
132 EUR excl. VAT159 EUR
  • For installation in switchboards
  • High precision
  • Suitable for increasing the immunity of the temperature sensor signal against interference over longer distances
  • Easy and fast configuration, reading and editing of data using a mobile phone with NFC without the need to power the transmitter
  • Data logger function
  • Digital input for calibration
  • Input/output galvanically isolated
  • Power supply directly from current loop
  • The Mypixsys configuration app for Android mobile phones can be freely downloaded from the Google Play Store
  • sample HERE
Analog outputYes
Record of measured quantityYes
Measured quantityTemperature
Power supply12-24 Vac/dc
Control inputTemperature sensor
ProducerPixsys
Output - relay0x

The temperature converter converts the signal obtained from Pt100, Ni100, K, S, R, J, T, N, B, E thermocouples and voltage to a standardized current analog signal of 4...20mA. It is designed for DIN rail mounting in a switchboard. The characteristics of these transmitters ensure high accuracy of temperature reading due to 16-bit precision A/D converter. At the same time, this solution allows the user to change the scale for the output signal.

Programming is done via RFid wireless technology (NFC) using an NFC-enabled mobile phone or the separately supplied programmer , which allows the operator to quickly perform all necessary calibrations and adjustments with the benefits of galvanic isolation thanks to wireless transmission technology. An app is available for Android mobile devices with NFC capability that allows you to program, adjust and view data in the field.

Non-volatile memory allows data logging with adjustable sampling frequency. Programming software (downloadable from the manufacturer's website) allows this data to be processed and the temperature curve to be displayed. Thanks to these features, this transmitter can also be used as a temperature logger.

TECHNICAL PARAMETERS
Pt100:
Measuring range
Resistance range
Connection

-200...+800°C
18,5...378 ?
2, 3, 4 wire
Ni100:
Measuring range
Resistance range
Connection

-50...+170°C
69...223 ?
2, 3, 4 wire
TC K:
Measuring range

-260...+1360°C
TC S:
Measuring range

-40...+1760°C
TC R:
Measuring range

-40...+1760°C
TC J:
Measuring range

-200...+1200°C
TC T:
Measuring range

-260...+400°C
TC N:
Measuring range

-260...+1280°C
TC B:
Measuring range

+40...+1820°C
TC E:
Measuring range

-260...+940°C
voltage:
Measuring range

-10...+70 mV
Dimensions 1 DIN module
Power supply 6...32 Vdc
Output 4...20 mA, 2µA resolution
Error output Adjustable, 21.5mA or 3.8mA
Output overcurrent protection approx. 30 mA
Maximum conversion error 0.1% of range or 0.2°C (higher of the two)
Line resistance 20? maximum
Temperature coefficient < 100 ppm
Sampling 300 ms
Response time (10...90%) approx. 600 ms
Coverage IP20
Standards CE, EN 61000-6-4, EN 61000-6-2
Operating conditions -40...+85°C
30...90% RH non-condensing