2000.35.010 Converts the signal from Pt100, Pt1000, Ni100 temperature sensors to a standardized analog current signal of 4...20 mA. Measured value recorder function. Programming and data download via RFid wireless transmission (NFC).
Temperature to 4 to 20 mA signal converter
Temperature to 4 to 20 mA signal converter
Temperature to 4 to 20 mA signal converter (1)
49,25 EUR 40,70 EUR excl. VAT
In stock
In person in Prague:nowWith a delivery company:tomorrow
Code1P-700-100PNvstup Pt100, Pt1000, Ni100, výstup 4..20 mA, napájení 6...32 VssProducerPixsysWarranty2 years

Pixsys RFid converter programmer

Pixsys RFid converter programmer
On request
132 EUR excl. VAT159 EUR
  • For mounting in DIN/B temperature probe sump heads
  • High accuracy
  • Suitable for increasing the immunity of the temperature sensor signal against interference over longer distances
  • Logger function
  • Power supply directly from the current loop
  • Easy and fast configuration, reading and editing of data using a mobile phone with NFC without the need to power the transmitter
  • The Mypixsys configuration app for Android mobile phones can be freely downloaded from the Google Play Store
Temperature sensor typePt100, TC
Measured quantityTemperature
Power supply12-24 Vac/dc
Control inputTemperature sensor
Output - relay0x
Analog outputYes
ProducerPixsys
Output voltage0-10 V
Record of measured quantityYes

The temperature transmitter in DIN/B head size converts the signal obtained from Pt100, Pt1000 or Ni100 probes (with two-, three-, four-wire connection) into a normalized current signal of 0...20mA. The characteristics of these transmitters ensure high accuracy of temperature reading due to the 16-bit precision A/D converter. At the same time, this solution allows to change the scale for the output signal.

Programming is done via RFid wireless technology (NFC) using an NFC-enabled mobile phone or the separately supplied programmer , which allows the operator to quickly perform all necessary calibrations and adjustments with the benefits of galvanic isolation thanks to wireless transmission technology. An app is available for Android mobile devices with NFC capability that allows you to program, adjust and view data in the field.

Non-volatile memory allows data logging with adjustable sampling frequency. Programming software (downloadable from the manufacturer's website) allows this data to be processed and the temperature curve to be displayed. Thanks to these features, this transmitter can also be used as a temperature logger.

TECHNICAL PARAMETERS
Pt100:
Measuring range
Resistance range
Connection

-200...+800°C
18,5...378 ?
2, 3, 4 wire
Ni100:
Measuring range
Resistance range
Connection

-50...+170°C
69...223 ?
2, 3, 4 wire
Pt1000:
Measuring range
Resistance range
Connection

-200...+800°C
185...3780 ?
2 wire
Dimensions O45 x 23 mm
Power supply 6...32 Vdc
Output 4...20 mA, 1µA resolution
Error output Adjustable, 21.5mA or 3.8mA
Output overcurrent protection approx. 30 mA
Maximum conversion error 0.1% of range or 0.2°C (higher of the two)
Line resistance 20? maximum
Temperature coefficient < 100 ppm
Sampling 300 ms
Response time (10...90%) approx. 600 ms
Coverage IP20
Standards CE, EN 61000-6-4, EN 61000-6-2
Operating conditions -40...+85°C
30...90% RH non-condensing