Power supply | 12 Vac/dc |
Design (panel size) | Other |
Type of regulation | On/off |
Control input | Temperature sensor |
Producer | Ascon Tecnologic |
Output - relay | 1x |
Display digit colour | Red |
Tecnologic E51 is a digital microprocessor controller designed for ON/OFF control of cooling, with the possibility of defrosting by stopping the compressor or heating. The E51A is a model that differs from the E51 in that it has no defrost option. The unit has 1 relay and 1 input for a PTC or NTC temperature sensor (depending on model, not parameter switchable).
Conforms to ECC directive 89/336 (EN55022: class B; EN61000-4-2: 8KV air, 4KV cont.; EN61000-4-3: 10V/m; EN61000- 4-4: 2KV supply, inputs, outputs; EN61000-4-5: supply 2KV com. mode, 1 KV diff. mode; EN61000-4-6: 3V), 2006/95/CE (EN 60730-1, EN 60730-2-7, EN 60730-2-9)
TECHNICAL PARAMETERS | |
---|---|
Power supply | 12 Vac/DC, +/- 10% 50/60Hz |
Power input | approx. 3 VA |
Input | 1x input for temperature sensor: PTC (KTY 81-121, 990? @ 25°C) |
Output | 1x switching relay 16A(6A) at 250 Vac, 1HP 250Vac |
Dimensions | 33 x 65 mm, depth 50 mm |
Degree of front panel protection | IP 65 (NEMA 3S) with gasket (not included) |
Operating conditions | 0 to 50 °C, max 95 RH% non-condensing |
Measuring range | PTC: -50 to 150 °C / -58 to 199 °F; NTC: -50 to 109 °C / -58 to 199 °F |
Display resolution | 1° or 0.1° (for a range of -19.9 ...19.9° |
Overall accuracy | +/- (0.5% of range + 1 digit) |
Sampling time | 130 ms |